  1. QUICK START
  2. Registers

ABB B21

Below the registers with the ABB B21 emulation firmware. More Eastron kWh meters using the same register configuration. This setup could be used in more configurations.

Default settings

The default dongle settings are:

9600 baud 8N1 ... modbus address 2

Register values are available in FC04, UINT32 and INT32

No value = 0, for example when U2 isn't available (single phase system) this value is 0.

Note

The mapping is made for the SMR 5 meters. This is common in EU but in the Netherlands versions 4 and 2 are available too.

Registers

register
description
value
Data type

0x5B00

Voltage phase 1

Volt * 10

UINT32

0x5B02

Voltage phase 2

Volt * 10

UINT32

0x5B04

Voltage phase 3

Volt * 10

UINT32

0x5B0C

Current phase 1

Ampere * 100

UINT32

0x5B0E

Current phase 2

Ampere * 100

UINT32

0x5B10

Current phase 3

Ampere * 100

UINT32

0x5B14

Active power total

Watt * 100

INT32

0x5B16

Active power phase 1

Watt * 100

INT32

0x5B18

Active power phase 2

Watt * 100

INT32

0x5B1A

Active power phase 3

Watt * 100

INT32

400*

DeviceID

default = 2

402*

Serial config

default = 8N1

404*

baudrate

default = 9600

406*

Pre40 (DSMR v2 meter)

1 = true / 0 = false

408*

Firmware version

1.3.0

410*

Hardware version

P1M3

PreviousEastron SDM630 EmulationNextUpdate

Last updated 20 days ago

= see for more information

FC03 device information