Registers

Minimal P1 Modbus Dongle firmware version for using with the Teltonika TeltoCharge = 1.2.1

update instruction : update

Default settings

The default settings are:

Modbus device id: 43

RS485 : 8E1 38k4 bps (8 bits, even, 1 stop, 38400 baud)

P1: 115200 8N1 = SMR v4 and v5 (EU) smart meters. Older smart meters (in the Netherlands v2/v3) use a additional power supply for the modbus dongle and FC06 register 6 should be true (1).

Registers

The Dongle supports FC03 and FC06 registers.

FC03 - P1 data

All registers are :

  • uint32 (4321) values

  • N/A = 0xFFFFFFFF

Registers 10, 12 and higher are implemented in firmware version 1.2.0+. Registers 38 - 48 are available from version 1.2.1.

FC03 - Device information

The registers below are available from firmware version 1.2.0.

FC06

Implemented in version 1.1.0+.

The serial config is a limited set and represented by a number. See below.

SERIAL_7N1 = 52

SERIAL_8N1 = 56

SERIAL_5N2 = 76

SERIAL_6N2 = 80

SERIAL_7N2 = 84

SERIAL_8N2 = 88

SERIAL_5E1 = 46

SERIAL_6E1 = 50

SERIAL_7E1 = 54

SERIAL_8E1 = 58

SERIAL_5E2 = 78

SERIAL_6E2 = 82

SERIAL_7E2 = 86

SERIAL_8E2 = 90

SERIAL_5O1 = 47

SERIAL_6O1 = 51

SERIAL_7O1 = 55

SERIAL_8O1 = 59

SERIAL_5O2 = 79

SERIAL_6O2 = 83

SERIAL_7O2 = 87

SERIAL_8O2 = 91