Installation
Select the installation instructions for your Smart Meter Modbus Adapter.
Last updated
Select the installation instructions for your Smart Meter Modbus Adapter.
Connections, power and physical controls differ by hardware. Use the page for your adapter:
D1MC — DIN-rail hardware with DSMR/P1 and HAN-NVE support, screw-terminal Modbus RTU and flexible 5 V power.
P1 Modbus Pro (NRGD) — compact adapter with an RS485 module and P1 output. Includes regular NRGD and ZAP2/NRGDH-based implementations with different A/B terminal positions; the latter also supports HAN-NVE using a HAN (RJ45)-to-RJ12 cable.
After installing the hardware, use the Device Manager and follow the shared firmware v2 configuration.
The old white P1 Modbus adapter has a micro-USB connector and a different fixed Modbus terminal pin-out. It has not been sold for years. Do not use its wiring diagram for current hardware; retain existing installation information only when servicing an old unit.
De-energize the installation before changing wiring.
Match A and B to the labels and instructions for both devices.
Use a suitable twisted pair and follow the connected equipment manufacturer's requirements for cable length, topology, grounding and shielding.
Configure the same device ID, baud rate and serial format on the adapter and Modbus master.
Apply 120 Ω termination only where required by the RS485 bus topology.