D1MC
Hardware, connections, power and installation for the D1MC DIN-rail Smart Meter Adapter.
D1MC is a configurable DIN-rail Smart Meter Adapter for fixed indoor installations. It currently converts DSMR/P1 and HAN-NVE meter data locally to Modbus RTU.
Linky TIC hardware interface present. Software support is planned and not yet available. Do not select or commission Linky TIC as a current firmware v2 meter source.
Connections and pin-out

The colors group terminals by purpose: blue identifies the Linky TIC/S0 signal terminals, red identifies 5 V and ground or reference terminals, and orange identifies the Modbus RTU data pair.
Linky TIC/S0 — blue
I2
Galvanically isolated signal input 2; use depends on the installed firmware
Linky TIC/S0 — blue
I1
Galvanically isolated signal input 1; use depends on the installed firmware
Power — red
GND
Ground connection for the 5 V supply group
Power — red
GND
Second ground connection for the 5 V supply group
Power — red
5 V
Input for an additional regulated 5 V supply
Modbus RTU — orange
A+
Modbus RTU data line A
Modbus RTU — orange
B-
Modbus RTU data line B
The Linky TIC/S0 terminals are physically present. Linky TIC software support is planned and not yet available in firmware v2. Do not infer a current Linky wiring procedure from the hardware pin-out alone.
Controls and interfaces

SMR/P1
Smart-meter input
RJ12 input for DSMR/P1 meters. HAN-NVE uses the same input with the appropriate optional adapter cable.
BUTTON
Local control
Short press to reboot; press for more than 5 seconds to restore factory settings; hold while applying power to enter download mode.
LED
RGB status LED
Shows operating state and diagnostics. Firmware v2 can adjust its brightness; see LED indicators.
USB
USB-C connection
Additional 5 V power, local Device Manager connection and firmware updates. Use a USB data cable for configuration and updates.
D1MC has no P1 output. It has software-controlled 120 Ω Modbus RTU termination, enabled by default.
Power options
DSMR/P1 version 5
5 V through the P1 connection, USB-C or the 5 V screw terminal
DSMR/P1 version 2 or 4
External regulated 5 V through USB-C or the 5 V screw terminal
HAN-NVE
External regulated 5 V through USB-C or the 5 V screw terminal
Linky TIC/S0 hardware
External regulated 5 V through USB-C or the 5 V screw terminal
Average consumption is 90 mA at 5 V. The power manager has a 500 mA protection limit; this is not the normal operating current.
Installation
D1MC is intended only for a dry indoor installation. Installation in or near electrical distribution equipment must be performed in accordance with applicable local rules by a person competent to do so.
Mount D1MC on the DIN rail with the installation de-energized.
Connect the supported meter interface:
connect a DSMR/P1 meter to the P1 input; or
connect HAN-NVE to the P1 input using the appropriate adapter cable.
Connect a regulated external 5 V supply when required by the table above.
Connect Modbus RTU using the labels on the screw terminal and the connected controller manufacturer's wiring instructions.
Apply power and connect through USB-C to the Device Manager.
Select the meter source and configure Modbus RTU in Configuration.
Confirm whether the default enabled 120 Ω termination is appropriate for D1MC's position on the RS485 bus.
Do not connect or commission the Linky TIC/S0 terminal as a current meter source until supported firmware and its installation instructions are published.
Last updated