D1MC

Hardware, connections, power and installation for the D1MC DIN-rail Smart Meter Adapter.

D1MC is a configurable DIN-rail Smart Meter Adapter for fixed indoor installations. It currently converts DSMR/P1 and HAN-NVE meter data locally to Modbus RTU.

Connections and pin-out

D1MC terminal pin-out for Linky TIC and S0, power and Modbus RTU
D1MC screw-terminal groups and terminal order, viewed from the front.

The colors group terminals by purpose: blue identifies the Linky TIC/S0 signal terminals, red identifies 5 V and ground or reference terminals, and orange identifies the Modbus RTU data pair.

Group
Terminal
Description

Linky TIC/S0 — blue

I2

Galvanically isolated signal input 2; use depends on the installed firmware

Linky TIC/S0 — blue

I1

Galvanically isolated signal input 1; use depends on the installed firmware

Power — red

GND

Ground connection for the 5 V supply group

Power — red

GND

Second ground connection for the 5 V supply group

Power — red

5 V

Input for an additional regulated 5 V supply

Modbus RTU — orange

A+

Modbus RTU data line A

Modbus RTU — orange

B-

Modbus RTU data line B

Controls and interfaces

D1MC smart-meter input, button, status LED and USB connection
D1MC front controls and interfaces.
Label
Feature
Description

SMR/P1

Smart-meter input

RJ12 input for DSMR/P1 meters. HAN-NVE uses the same input with the appropriate optional adapter cable.

BUTTON

Local control

Short press to reboot; press for more than 5 seconds to restore factory settings; hold while applying power to enter download mode.

LED

RGB status LED

Shows operating state and diagnostics. Firmware v2 can adjust its brightness; see LED indicators.

USB

USB-C connection

Additional 5 V power, local Device Manager connection and firmware updates. Use a USB data cable for configuration and updates.

D1MC has no P1 output. It has software-controlled 120 Ω Modbus RTU termination, enabled by default.

Power options

Meter interface
Power requirement

DSMR/P1 version 5

5 V through the P1 connection, USB-C or the 5 V screw terminal

DSMR/P1 version 2 or 4

External regulated 5 V through USB-C or the 5 V screw terminal

HAN-NVE

External regulated 5 V through USB-C or the 5 V screw terminal

Linky TIC/S0 hardware

External regulated 5 V through USB-C or the 5 V screw terminal

Average consumption is 90 mA at 5 V. The power manager has a 500 mA protection limit; this is not the normal operating current.

Installation

  1. Mount D1MC on the DIN rail with the installation de-energized.

  2. Connect the supported meter interface:

    • connect a DSMR/P1 meter to the P1 input; or

    • connect HAN-NVE to the P1 input using the appropriate adapter cable.

  3. Connect a regulated external 5 V supply when required by the table above.

  4. Connect Modbus RTU using the labels on the screw terminal and the connected controller manufacturer's wiring instructions.

  5. Apply power and connect through USB-C to the Device Manager.

  6. Select the meter source and configure Modbus RTU in Configuration.

  7. Confirm whether the default enabled 120 Ω termination is appropriate for D1MC's position on the RS485 bus.

Do not connect or commission the Linky TIC/S0 terminal as a current meter source until supported firmware and its installation instructions are published.