Firmware v2 register mappings

Complete firmware v2 mapping and register reference.

Firmware v2 contains all selectable mapping profiles in one firmware image. Selecting a mapping changes only the exposed register model. It does not change the Modbus device ID, baud rate or serial format.

Global communication settings

The factory defaults are device ID 43, 38400 baud and 8E1. These are global settings and can be changed independently in the Device Manager.

Both FC03 and FC04 read the active mapping. The preferred configuration method is the Device Manager. Firmware v2 also accepts these global FC06 writes:

Address
Setting
Values

0

Device ID

1-254

2

Serial format offset

46-91

4

Baud-rate index

0-4 = 9600, 19200, 38400, 57600, 115200

8

Mapping

Mapping value from the table below

Mapping overview

Value
Mapping
Profile
Firmware 2.3.0 status

1

SDM630

Active

2

DTSU666

Active

3

ALFEN

Active

4

EM330

Active

14

EM111

Active

5

ABB_B21

Active

6

EMPRO

Active

7

P1M_F

Active

8

KLEFR

Active

10

CHARGE

No recipe assigned in 2.3.0

11

DRIS

No recipe assigned in 2.3.0

12

XEMEX

Active

13

SE

Active

15

SUNSPEC203

Active

Register table conventions

Each mapping page is generated from the active firmware v2 recipe and profile definitions. Addresses are shown in decimal and hexadecimal. A 32-bit value occupies two consecutive 16-bit Modbus registers.