Schneider Charge Pro emulation

This mapping emulates the Schneider Charge Pro layout that is used for charger integrations.

Defaults

  • Modbus device id: 16

  • RS485: 9600 8E1

  • Function codes: FC03

  • Data types: mixed uint16 and uint32

Measurement registers

Register
Description
Type
Unit / encoding

761

voltage_l1

uint32

V

763

voltage_l2

uint32

V

765

voltage_l3

uint32

V

767

current_l1

uint16

A

769

current_l2

uint16

A

771

current_l3

uint16

A

773

power_delivered_l1

uint32

W

775

power_delivered_l2

uint32

W

777

power_delivered_l3

uint32

W

779

power_returned_l1

uint32

W

781

power_returned_l2

uint32

W

783

power_returned_l3

uint32

W

Notes about the current layout

  • The current registers are served with mixed word widths.

  • Registers 768, 770 and 772 are filler 16-bit words used to keep the current values aligned.

Device info

Register
Description
Value

400

device id

current DevID

402

serial config

encoded serial mode

404

baudrate

actual baudrate

406

pre4 meter flag

0 or 1

408

firmware version

packed MMmmpp

410

dongle name

packed P1M3