Default float mapping

This is the default FLOAT emulation mapping. It exposes a compact float-based layout.

Defaults

  • Modbus device id: 1

  • RS485: 9600 8E1

  • Function codes: FC03

  • Data format: mostly float32, plus a few uint32 status registers

  • Address range: 0-52

Registers

Register
Description
Type
Unit / encoding

0

sample timestamp

uint32

epoch UTC

2

energy_delivered_tariff1

float32

kWh

4

energy_delivered_tariff2

float32

kWh

6

energy_returned_tariff1

float32

kWh

8

energy_returned_tariff2

float32

kWh

10

energy_delivered_total

float32

kWh

12

energy_returned_total

float32

kWh

14

power_delivered

float32

kW

16

power_returned

float32

kW

18

net_power_total

float32

W

20

voltage_l1

float32

V

22

voltage_l2

float32

V

24

voltage_l3

float32

V

26

current_l1

float32

A, negative when returning on L1

28

current_l2

float32

A, negative when returning on L2

30

current_l3

float32

A, negative when returning on L3

32

gas timestamp

uint32

epoch UTC

34

gas delivered

float32

m3

36

tariff

uint32

numeric tariff id

38

peak power last quarter

float32

meter value

40

net_power_l1

float32

W

42

net_power_l2

float32

W

44

net_power_l3

float32

W

46

water delivered

float32

m3

48

identifier

uint32

fixed P1DO = 0x5031444F

50

firmware version

uint32

packed MMmmpp

52

online flag

uint32

1 = online, 0 = offline

Notes

  • Missing float values are returned as NaN.

  • Missing integer values use 0xFFFFFFFF.

  • This mapping is useful when the Modbus client expects engineering values directly as floats.

Last updated